IT Cooling Systems and Cooling Solutions
There are various methods available for cooling server rooms and data centers. The most suitable cooling solution depends, among other factors, on the heat load, power density, building structure, and availability requirements. We explain the most important systems and show when air cooling, free cooling, liquid cooling, or combined solutions are appropriate.
As power densities in data centers increase, liquid cooling is becoming increasingly important. In particular, high-performance systems for artificial intelligence and high-performance computing can generate heat loads that can only be dissipated using conventional air-based designs with very high airflow rates.
However, this does not mean that air cooling will be completely replaced by liquid cooling. Which method is suitable depends primarily on the IT hardware used, the power output of individual racks, the existing infrastructure, and the requirements of the respective data center.
How do air cooling and liquid cooling differ?
In air cooling, heat from the IT components is transferred to an air stream. The heated air is then fed into a cooling system, cooled, and returned to the IT area. Sufficient airflow and controlled separation of cold and warm air are critical here.
In liquid cooling, on the other hand, heat is absorbed entirely or partially via a liquid directly on or in the immediate vicinity of the IT components. A common method is direct-to-chip cooling, in which, for example, processors or other particularly heavily loaded components are cooled via heat sinks.
Since liquids can transport heat much more efficiently than air, such systems are particularly well-suited for very high power densities.
When does air cooling remain a viable option?
For many server rooms and data centers, air cooling remains a technically sound solution. This is especially true when the existing heat loads can be reliably dissipated with reasonable air volumes.
Advantages can arise particularly with traditional air-cooled IT hardware. Heat is dissipated without fluid connections directly to the servers, and existing IT infrastructures can often be used further without fundamental changes to the cooling principle.
This can also be an important advantage when modernizing existing server rooms. Through optimized airflow, larger heat exchanger surfaces, or more powerful heat removal systems, the existing air cooling can be adapted to meet increasing demands.
Added to this is the possibility of using free cooling under suitable operating and outdoor conditions, thereby reducing the use of mechanical cooling.
When is liquid cooling the better choice?
The higher the power of a single rack, the greater the required air volume flow becomes with air cooling alone. At some point, the required air volumes, flow cross-sections, and fan capacities may become technically or economically impractical.
Especially with very high power densities in AI and HPC systems, liquid cooling can therefore offer advantages. Heat is absorbed closer to its source and does not have to be transported entirely through the room air.
However, this requires that the IT hardware used be designed for the respective liquid cooling system and that the necessary infrastructure for distribution, heat transfer, monitoring, and operation be in place.
The decision should therefore not be based solely on a specific rack power rating. The decisive factor is the overall system comprising IT hardware, power density, cooling technology, and infrastructure.
Why are hybrid cooling concepts becoming more important?
Air and liquid cooling do not have to be viewed as competing systems. In modern data centers, both methods can be combined.
High-load processors or entire high-density systems can, for example, be cooled using liquid cooling, while traditional servers, storage, and network components continue to operate using air cooling.
Even with direct-to-chip cooling, a heat load may remain in the room. Not all components of a server necessarily transfer their heat to the liquid cooling loop. Supplemental air cooling may therefore still be required.
Hybrid data centers thus make it possible to provide different power densities within the same infrastructure with their respective appropriate cooling methods.
Customized Air Cooling for Server Rooms and Data Centers
HANSA focuses on air-based cooling systems for IT cooling and currently does not offer direct-to-chip liquid cooling. However, where heat loads can be effectively dissipated via air, cooling systems can be customized to the specific project. Among other factors, air flow rate, heat exchanger surface area,
Among other factors, airflow capacity, heat exchanger surfaces, unit dimensions, airflow patterns, refrigerant supply, redundancy, and control systems can be adapted to the requirements of the server room or data center. This customized design also enables solutions that go beyond traditional, standardized cooling units.
This customized design also enables solutions that go beyond traditional, standardized cooling units. One example is large-scale cooling walls, in which high air volumes are cooled via appropriately dimensioned heat exchanger surfaces. We discuss this principle in more detail in the article on cooling walls in data centers.
Whether air cooling, liquid cooling, or a combination of both methods is suitable should therefore be determined based on the actual IT infrastructure. Air cooling remains particularly attractive in situations where it can dissipate the required heat loads reliably, efficiently, and with a reasonable level of technical effort.
Free Cooling in Data Centers – How It Works and Applications
Server rooms and data centers require cooling for much of the year— even when outdoor temperatures are low. This is exactly where free cooling comes in: Suitable outdoor conditions are used to dissipate heat from IT equipment with as little use as possible of mechanical cooling.
“Free cooling” does not mean that no electrical energy is needed. Fans, pumps, and control systems still require energy. The main advantage is that the mechanical refrigeration system can be shut down completely under suitable outdoor conditions, or at least significantly reduced in load.
How does free cooling work?
A prerequisite for free cooling is a sufficient temperature difference between the IT area to be cooled and the surrounding environment. If the outdoor conditions are favorable, the heat can be dissipated into the environment with little or no use of a chiller.
How often this is possible over the course of the year depends, among other things, on the location, outdoor temperatures, the IT heat load, and the required operating temperatures. The sizing of heat exchangers, air ducts, and fans also influences the usable operating hours of free cooling.
Generally, a distinction can be made between direct and indirect free cooling. HANSA offers different system designs for both methods.
What is direct free cooling?
In direct free cooling, suitable outdoor air is used directly to cool the server or equipment room. If the outside air is cool enough, it is introduced into the area to be cooled, where it absorbs the heat and is then discharged back outside as warmed exhaust air. This principle allows for a very direct use of low outside temperatures. At the same time, the outside air comes into direct contact with
This principle enables very direct utilization of low outdoor temperatures. At the same time, the outdoor air comes into direct contact with the area to be cooled. Air quality, filtration, humidity, and other environmental conditions must therefore be taken into account during the planning phase.
HANSA uses direct free cooling in, among others, the unit series: Slim Line and Free Line.
- Slim Line: compact heat removal units, particularly for small and medium-sized server and equipment rooms.
- Free Line: customizable units for direct free cooling for larger air volumes and project-specific applications.
If outdoor conditions are insufficient for free cooling, mechanical cooling can be used as a supplement, depending on the system design. This allows the freely available outdoor air to be used for heat removal for as long as possible. How does indirect free cooling work?
How does indirect free cooling work?
With indirect free cooling, outdoor air and the air in the data center remain separate from one another. Heat is transferred to the outdoor air via a heat exchanger. The air in the IT area can thus be recirculated.
The advantage is that low outdoor temperatures can be utilized without introducing outdoor air directly into the server room. Dust, contaminants, or other external environmental factors thus do not enter the IT area directly. HANSA utilizes this principle in the Blue Line IT series of devices.
HANSA uses this principle in its Blue Line IT series. The warm air from the server or equipment room is cooled by the cooler outside air via the integrated heat recovery system and then recirculated back into the IT area. Outside air and recirculated air remain separate from one another.
Depending on the model, heat transfer in the Blue Line IT system can take place via a rotor or via a double cross-counterflow plate heat exchanger. Under appropriate outdoor conditions, the outdoor air can also be adiabatically cooled. If the cooling capacity achievable in this way is not sufficient, a cooling coil can provide the necessary additional cooling.
When is additional mechanical cooling required?
Outdoor conditions are not sufficient at every location and during every season for complete free cooling. At higher outdoor temperatures, additional mechanical cooling may therefore be required. Combined systems are particularly interesting. At low outdoor temperatures, free cooling handles heat removal. If the outdoor temperature rises, mechanical cooling can be activated as needed.
Combined systems are particularly interesting. At low outdoor temperatures, free cooling handles heat removal. If the outdoor temperature rises, mechanical cooling can be activated as needed.
Therefore, energy efficiency is not determined solely by the design scenario on particularly hot days. Equally important is the energy consumption of the cooling system during the many hours when outdoor temperatures are lower.
How significant can the energy savings from free cooling be?
The potential energy savings depend heavily on the location, outdoor temperatures, heat load, temperature level, and system design. It is therefore not possible to provide a universal percentage figure.
However, a calculation by HANSA for a mechanical room with a 15 kW cooling demand illustrates the potential. Based on the temperature distribution according to DIN 4710 for Frankfurt am Main, a Slim Line Q15 with direct free cooling was compared to a recirculating air chiller with comparable mechanical cooling capacity.
In this calculation, the recirculating air chiller results in an annual electrical energy consumption of approximately 40,550 kWh. For the Slim Line Q15, the consumption is approximately 9,671 kWh, including mechanical cooling and fans.
In this specific calculation example, this corresponds to a reduction in electric energy consumption of approximately 76%. The main reason for this is that mechanical cooling is not required during a large part of the year.
The results cannot be generalized to other locations, heat loads, or systems. However, they demonstrate the extent to which the consistent use of low outdoor temperatures can influence the annual energy consumption of IT cooling. You can find the calculation basis and further details on our page on the cost-effectiveness of IT cooling.
What impact do temperatures in the data center have?
How long free cooling can be used also depends on, what temperatures the cooling system must maintain. If unnecessarily low temperatures are required, the outside air can only be used for complete heat dissipation during correspondingly cooler weather conditions.
Conversely, if the temperature ranges permitted for the IT equipment in use are utilized effectively, the operating times for free cooling can increase. The temperature strategy of the data center thus directly influences the energy efficiency of the cooling system.
Why is free cooling control important?
Outdoor temperature and IT load change continuously. Accordingly, cooling capacity should also be adjusted to actual demand.
A suitable control system regulates fans and other components as needed and determines when free cooling is sufficient and when additional cooling is required. This allows the energy-saving potential of free cooling to be harnessed without compromising the necessary operating conditions of the IT systems.
Which HANSA solution is suitable for which type of free cooling?
HANSA offers various system designs for free cooling in server rooms, technical facilities, and data centers. Which solution is suitable, depends in particular on the heat load, the required air volume, space constraints, and the requirements for separating outdoor and indoor air.
- Slim Line: compact units with direct free cooling for server and equipment rooms.
- Free Line: custom-configurable units with direct free cooling for larger and project-specific applications.
- Blue Line IT: custom-designed systems with indirect free cooling and separation of outdoor and recirculated air via heat recovery.
The key factor here is not just the individual cooling unit. Free-air cooling, mechanical refrigeration, heat exchangers, fans, airflow management, and control should be considered as a complete system. The goal is to utilize free cooling for as long as possible and to use additional refrigeration only when it is actually needed.
A cooling wall is a special type of air-based data center cooling system. Instead of housing the required heat exchange surfaces in relatively compact recirculating air cooling units, a large portion of a wall surface is used for cooling. This provides large heat exchange surfaces and flow cross-sections.
This provides large heat exchange surfaces and flow cross-sections . Large volumes of air can be moved with comparatively low flow resistance. This makes cooling walls particularly attractive for data centers where larger heat loads are still to be dissipated via air.
How does a cooling wall work?
The basic operating principle is similar to that of a traditional air-cooled unit. The air heated by the servers is directed via fans to the cooling system and passed through large-surface-area heat exchangers.
The heat from the air is typically transferred to a water circuit. The cooled air is then returned to the intake side of the IT equipment.
The main difference lies in the design. Heat exchangers and fans can be distributed across large wall surfaces instead of being limited to the cross-section of individual cooling units.
What are the advantages of a large heat exchanger surface area?
A large heat exchanger surface area makes it possible to pass high air volumes through comparatively large free cross-sections. This allows for a reduction in air-side pressure losses and more favorable operating conditions for the fans.
At the same time, large heat exchanger surfaces can transfer high heat loads even at relatively small temperature differences. This can allow for higher cooling water temperatures and thus also improve the efficiency of the upstream refrigeration or recooling technology. The extent of these advantages depends on the design of the heat exchanger, the air flow rates, the water temperatures, and the overall system design.
The extent of these benefits depends on the design of the heat exchanger, the air flow rates, the water temperatures, and the overall system design.
How is a cooling wall integrated into the data center?
Cooling walls can be part of the physical separation between the warm and cold zones of the data center. The warm server exhaust air is collected, passed through the heat exchangers, and then returned to the IT equipment as cooled air.
Depending on the room layout, the air can, for example, be routed through a raised floor, a ceiling area, or directly through a cold aisle or hot aisle.
Controlled airflow is crucial. The less the cooled and heated air mix uncontrollably, the more precisely the cooling capacity can be utilized.
When is a cooling wall a good option?
Cooling walls are particularly useful when large heat loads need to be dissipated via air and there is sufficient space available for a large-scale cooling solution.
Possible applications include larger data centers with air-cooled IT, as well as existing facilities where the existing cooling capacity needs to be increased or the airflow needs to be reorganized. The concept can also serve as an attractive solution between traditional air-cooled units and a complete transition to liquid cooling.
The concept can also serve as an attractive compromise between traditional air-circulation cooling units and a complete transition to liquid cooling. As long as the IT equipment in use releases most of its heat into the ambient air, large-scale air cooling can be a viable option even with increasing heat loads.
Is a cooling wall the same as liquid cooling?
No. Even though the heat exchanger in a cooling wall is typically operated with water, it still constitutes a form of air cooling for the IT equipment.
The servers first transfer their heat to the air. Only at the cooling wall is this heat transferred from the air to the cooling water. Therefore, there are no fluid connections to the individual servers.
This is different with direct-to-chip liquid cooling. In that case, the heat is absorbed directly from particularly heavily loaded IT components via a liquid circuit.
Can a cooling wall be combined with free cooling?
A cooling wall primarily describes the type of heat transfer within the data center. How the heat absorbed by the cooling water is subsequently dissipated into the environment is, in principle, independent of this.
Under suitable outdoor conditions, for example, an air-cooled heat exchanger can provide the necessary cooling water with little or no use of mechanical refrigeration. At higher outdoor temperatures, a chiller can be used as a supplement.
This also allows a cooling wall to be integrated into an overall concept that includes natural and mechanical cooling.
Custom Cooling Walls from HANSA
HANSA does not currently offer cooling walls as a separate, standardized product series. However, through the custom design and manufacture of HVAC and IT cooling units, the technical principle can be implemented on a project-specific basis.
Heat exchanger surfaces, fans, airflow rates, dimensions, and unit layout can be tailored to the spatial conditions and the required cooling capacity of the data center. Control systems and redundancy can also be designed according to the requirements of the respective project.
This customized planning is particularly advantageous for cooling walls, since available wall space, airflow paths, rack layout, and power densities vary from data center to data center.
The cooling wall should therefore be understood not as a single standard unit, but rather as part of an air-cooling concept tailored to the data center.
A high-performance cooling system alone does not guarantee that all servers will be sufficiently cooled. It is equally important that the cooled air actually reaches the intake side of the IT components and that heated exhaust air is returned as directly as possible to the cooling system .
The cold aisle/hot aisle principle creates an organized airflow pattern for this purpose. Through the strategic arrangement of the server racks, cold and warm air zones are separated from one another, and unwanted mixing is reduced.
How do cold aisles and hot aisles work?
Server racks are arranged so that their intake sides and exhaust sides face each other. The cold aisle is formed between the intake sides, while the hot aisle is formed between the rear sides of the servers. The cooled air is fed into the cold aisle and drawn in by the servers.
The cooled air is fed into the cold aisle and drawn in by the servers; as it flows through the IT equipment, it absorbs heat and exits; at the rear at a higher temperature. This heated air is then returned to the cooling system.
This creates a defined airflow path: cooling system – cold aisle – servers – hot aisle – cooling system.
Why should cold and warm air be kept separate?
If cold supply air and warm exhaust air from the servers mix uncontrollably, cooling efficiency deteriorates. Some of the air that has already been cooled may flow back to the cooling system without first having passed through a server. At the same time, warm exhaust air may re-enter the intake side of the IT equipment.
This can result in local areas with elevated inlet temperatures, even though there is sufficient cooling capacity available for the room as a whole.
Controlled airflow reduces such airflow short-circuits. This allows the available cooling capacity to be utilized more effectively, rather than having to compensate for unfavorable airflow with a lower supply air temperature or larger air volumes.
What are the benefits of a cold aisle or hot aisle containment system?
A simple cold aisle–hot aisle configuration reduces the mixing of airflows, but does not prevent it entirely. An additional enclosure can separate cold and hot areas even more effectively.
With a cold aisle containment system, the area with the cooled supply air is spatially confined. With a hot aisle containment system, on the other hand, the heated server exhaust air is captured and specifically returned to the cooling system.
Which concept is more suitable depends, among other things, on the building structure, the air supply, the rack layout, and the cooling system used. What matters most is not so much the name of the system as the extent to which the two airflows are separated as completely as possible.
What are bypass air and recirculation?
Two typical problems associated with poor airflow are bypass air and recirculation.
- Bypass air: Cooled air returns to the cooling system without first flowing through the IT components and absorbing heat.
- Recirculation: Server exhaust air that has already been heated re-enters the intake side of the IT equipment, where it increases the inlet temperature.
Both effects should be minimized as much as possible. In this context, it is not only cold and hot aisles that play a role. Open vertical spaces in racks, cable penetrations, floor openings, and other uncontrolled airflow paths can also influence airflow.
Why must the airflow volume match the servers’ requirements?
The cooling system must provide sufficient air to absorb the resulting heat load. At the same time, the air should be available as much as possible there where it is needed by the servers.
A very high airflow volume alone does not solve the problem of poor distribution. If individual areas are oversupplied and others undersupplied, local hotspots can develop despite an adequate total airflow volume.
When dealing with varying rack power ratings, it is therefore important to consider that not every area of the data center has the same air demand. Sensors and demand-based control can help adapt operations to the actual load conditions.
How does airflow affect energy efficiency?
Effective separation of cold and warm air can make better use of the temperature difference between supply and return air. As the air passes through the IT equipment, it absorbs heat in a targeted manner and then returns to the cooling system at a higher temperature.
This allows the heat exchangers and cooling system to operate under more favorable conditions. At the same time, it reduces the need to provide unnecessarily large air volumes or to cool the supply air more extensively simply to compensate for airflow problems.
Airflow and energy efficiency should therefore be considered together as early as the planning stage of the data center.
How are airflow and the cooling system related?
Optimal airflow also depends on how the cooled air is supplied and how the warm air is returned. An air supply via a raised floor poses different challenges than a direct supply into the cold aisle or a system with a large-area cooling wall.
Therefore, rack layout, cold and hot aisles, the cooling system, and airflow paths should not be planned independently of one another. Especially in the case of high heat loads, early coordination can prevent the need to later route large volumes of air through unfavorable or insufficiently large flow cross-sections.
Custom Airflow Planning with HANSA
For custom-designed data centers, the cooling system must also be able to adapt to the existing spatial conditions. HANSA therefore manufactures IT cooling units in both standardized and project-specific designs.
Unit dimensions, air connections, airflow rates, fan arrangement, and control systems can be tailored to the respective airflow design concept. Particularly in large or spatially challenging installations, such a customized design can help avoid unnecessary air diversions and pressure losses.
HANSA also supports the planning process with 3D models. This is particularly helpful for existing buildings or in confined spaces, allowing the unit, air pathways, and existing building structures to be coordinated early on.
Free cooling can significantly reduce a data center’s energy consumption. However, it does not provide sufficient capacity under all outdoor conditions. If the outdoor temperature or the heat load increases, the required cooling capacity may need to be supplemented by mechanical refrigeration.
There are various options here: The refrigeration system can be integrated directly into the cooling unit, or the cooling can be generated centrally via an external chiller. In addition, natural and mechanical cooling can be combined into a hybrid system. Integrated refrigeration system or external chiller?
Integrated refrigeration system or external chiller?
Mechanical cooling does not necessarily have to be generated directly within the IT cooling unit. Basically, two different system concepts can be distinguished.
In an integrated cooling system, the main cooling cycle is located directly in or on the cooling unit. This allows the unit to be designed as a largely optimized system unit. The absorbed heat is dissipated to the environment via a condenser.
Alternatively, the IT cooling unit can be equipped with a chilled water coil. The actual cooling then takes place outside the unit, for example, via a central chiller. The cooled water is fed to the heat exchanger of the IT cooling unit, where it absorbs the heat from the ambient air.
Which variant is more suitable depends, among other things, on the required cooling capacity, the existing infrastructure, redundancy requirements, space constraints, and the desired system design.
What are the advantages of an external chilled water supply?
With a central chilled water supply, the IT cooling unit and the chiller are hydraulically connected to each other, but the refrigerant circuit is located within the chiller. This allows air cooling and refrigeration to be technically separated from one another.
This can be particularly advantageous for larger systems. Multiple cooling units can be supplied via a shared chilled water network. At the same time, the central refrigeration system can be designed to meet the project’s requirements and, if necessary, modernized independently of the air-side cooling units. This
This concept also offers flexibility with regard to the selection of the refrigerant. The choice of refrigerant used in the chiller is not directly dictated by the air-side IT cooling unit. When planning or later upgrading the refrigeration system, different technical solutions can therefore be considered.
What is the significance of the F-Gas Regulation for refrigeration systems?
The European F-Gas Regulation tightens the requirements for fluorinated refrigerants and is gradually leading to stricter restrictions on refrigerants with high global warming potential. The choice of refrigerant is therefore becoming increasingly important in the planning and modernization of refrigeration systems.
An external chilled water supply can provide additional flexibility here: The IT cooling unit itself operates on the refrigeration side with water or a suitable water-glycol mixture on the cooling side, while the selection of the refrigerant is made at the level of the chiller. This allows the cooling system to be selected or later upgraded in accordance with technical,
This allows the refrigeration system to be selected or later updated in accordance with technical, regulatory, and operational requirements without necessarily having to replace the air-side cooling units as well.
Which refrigerants and system designs are appropriate and permissible for a specific project must be evaluated on a case-by-case basis based on current regulatory requirements and technical constraints.
What does hybrid cooling mean in a data center?
In a hybrid cooling concept, different methods are combined. Of particular interest is the combination of free cooling and mechanical cooling.
Depending on outdoor conditions and the heat load, different operating modes can be utilized:
- Free cooling: Outdoor conditions are sufficient to provide the required cooling capacity without compressor operation.
- Mixed operation: Natural cooling handles a portion of the heat load, while mechanical cooling provides the remaining cooling capacity.
- Mechanical cooling: Under unfavorable outdoor conditions, the required cooling capacity is provided predominantly or entirely by the refrigeration system.
The goal is to use free cooling, which is more energy-efficient, for as long as possible, and to supplement it with mechanical cooling only as needed.
Why is mixed operation beneficial?
Free cooling and mechanical cooling do not have to be viewed exclusively as two separate operating modes. Often, low outdoor temperatures can already provide part of the required cooling capacity, even though they are no longer sufficient for complete free cooling. In this operating range, mechanical cooling need only handle the remaining cooling load.
In this operating range, mechanical cooling need only handle the remaining cooling load. For annual energy efficiency, therefore, it is not only operation on particularly hot days that is decisive, but the behavior of the entire system over the course of the entire year.
What role does the control system play?
The control system plays a key role in determining how efficiently a combined cooling system operates. It must detect the current cooling demand and deploy the available cooling methods accordingly.
In doing so, factors such as outdoor, supply, and return air temperatures, the current heating load, and the operating states of fans and refrigeration units can be taken into account.
Free cooling, fans, and mechanical refrigeration should therefore not be viewed as independent components, but rather as a single, jointly controlled system. Which HANSA solution is suitable for which cooling concept?
Which HANSA solution is suitable for which cooling concept?
Depending on the requirements, different HANSA unit concepts can be used:
- Slim Line: compact IT cooling units in which free and mechanical cooling can be combined.
- Free Line: individually configurable heat removal units for larger and project-specific applications with free cooling and supplementary mechanical cooling.
- ReCool Line: Recirculating air cooling units, optionally with their own refrigeration system or chilled water coils for integration into an external chilled water supply.
- Blue Line IT: custom-designed systems for larger data centers, in which different methods of heat removal and refrigeration supply can be combined on a project-specific basis.
Outdoor air cannot or should not be used directly for cooling in every project. Structural conditions, air purity requirements, or climatic constraints may necessitate the use of recirculating air cooling alone.
For such applications, HANSA offers the ReCool Line. The recirculating air cooling units can be configured either with an integrated refrigeration system and external condenser or with a chilled water coil for integration into an existing or central chilled water supply.
This allows the cooling concept to be adapted to the existing infrastructure. If a central chilled water supply is already in place or if chilled water generation is to be deliberately planned separately, the chilled water variant can be used. If, on the other hand, a compact, coordinated solution is desired, a variant with its own refrigeration system is recommended.
Which system is suitable therefore does not depend solely on the maximum cooling capacity required. Equally important are the location, IT power density, existing cooling supply, redundancy, energy efficiency, space constraints, and the long-term system strategy.