Fundamentals of IT Cooling
Servers, storage systems, and network equipment continuously generate heat during operation, which must be reliably dissipated. In "The Basics of IT Cooling," we explain how server rooms and data centers are cooled, how cooling requirements can be determined, and what cooling demands different IT infrastructures place on the system.
Servers, storage, network, and other IT components require electrical power. A large portion of this energy is ultimately released into the environment as heat during operation. This heat must be continuously and reliably removed from the server room or data center.
Without adequate cooling, the temperature of the air drawn in by the IT components rises. Excessively high temperatures can deteriorate the operating conditions of the IT systems and, in the worst-case scenario, lead to reduced performance or outages. Cooling is therefore a key component of the fundamental technical infrastructure of a data center.
Where does the heat come from in a data center?
The primary heat load is generated by the IT equipment itself. Processors, memory, power supplies, network components, and other electronic components generate heat during operation.
Added to this are other heat loads, such as those from electrical systems, lighting, or people. However, the most critical factor in designing the cooling system is the electrical power consumed by the installed IT equipment and the power consumption expected in the future. With increasing computing power, the heat load can become concentrated in ever-smaller areas and individual racks. Therefore, it is not sufficient to consider only the total power of a data center.
As computing power increases, the heat load can become concentrated in increasingly smaller areas and individual racks. Therefore, it is not sufficient to consider only the total power of a data center. The spatial distribution of heat loads is also important for the cooling design.
How is heat removed from a server room?
In traditional air cooling, large volumes of air absorb the heat from the IT components. The heated air is then directed to a heat removal unit, where it is cooled and returned to the IT area.
It is crucial to ensure that the airflow path is as controlled as possible. The cooled air should reach the servers where it is needed, and the heated air should be returned to the cooling system as directly as possible. Uncontrolled mixing can result in air that has already been heated by the IT components being drawn in again.
That is why cooling equipment and airflow management are always part of a unified cooling concept. Cold aisles and hot aisles, enclosures, or other forms of airflow management can help separate cold and warm airflows from one another.
Does cooling need to be available around the clock?
IT systems generate heat as long as they are in operation. For IT systems in continuous operation, the necessary heat dissipation must therefore be ensured continuously.
The level of cooling availability required depends on the importance of the respective IT infrastructure. For business-critical applications and data centers, therefore, redundant cooling concepts are often provided so that operations can continue even during maintenance work or in the event of individual component failures. The
The level of redundancy required must be determined on a project-by-project basis. We cover this topic in more detail in the section on planning and operational reliability.
Why isn’t more cooling automatically better?
The goal of IT cooling is not to keep a server room as cold as possible; rather, it is crucial to reliably maintain the operating conditions required for the IT equipment in use. Unnecessarily low temperatures can increase the energy consumption of the cooling system;
Unnecessarily low temperatures can increase the energy consumption of the cooling system and limit the possibilities for energy-efficient operation. At the same time, it is essential to prevent individual areas or racks from experiencing excessively high supply air temperatures due to poor air distribution. At the same time, it is essential to prevent individual areas or racks from experiencing excessively high supply air temperatures due to poor airflow distribution.
Effective IT cooling therefore combines sufficient cooling capacity with appropriate airflow management and a control system that responds to the actual operating conditions.
Is air cooling still suitable for modern data centers?
Air cooling remains an important cooling method for server rooms and data centers. Whether it is suitable for a specific application, depends in particular on the power density of the IT equipment, the distribution of the heat loads, and the hardware used.
As rack power increases, so does the volume of air required to dissipate the heat. At very high power densities, such as those that may occur, for example, in certain AI and HPC systems, direct liquid cooling is therefore gaining importance.
However, this does not mean that air cooling will generally be replaced by liquid cooling. For many server rooms and data centers, an efficiently designed air cooling system remains a technically sound solution. Hybrid concepts are also possible, in which components under particularly heavy load are liquid-cooled, while the remaining heat loads continue to be dissipated via the ambient air.
We discuss the differences between air cooling and liquid cooling, as well as their respective applications, in greater detail in the section on cooling systems and cooling concepts.
What is the most important factor in cooling overall?
A suitable cooling concept starts with the actual IT load. In addition to the total cooling capacity, the power density of individual racks, airflow, the desired availability, and possible future expansions must be taken into account.
Only on this basis can a decision be made as to which cooling method and which equipment are suitable for a server room or data center. A project-specific analysis is therefore more sensible than the blanket selection of a specific cooling system.
The required cooling capacity of a server room or data center is determined by the heat that must be dissipated during operation. The installed IT equipment typically accounts for the largest portion of this heat. IT equipment.
However, for a reliable design, it is not enough to simply consider the current power consumption of the servers. Actual operating power, other heat sources, load distribution, and planned expansions must also be taken into account.
How are electrical power and heat load related?
The electrical energy consumed by servers, storage devices, and network components is ultimately converted almost entirely into heat. The electrical power consumption of the IT infrastructure is therefore an important basis for determining the required cooling capacity.
For example, if the IT system continuously draws an electrical power of 100 kW, this heat must also be removed from the IT area during operation. For the sizing of a complete cooling system, additional relevant heat loads and operating conditions must be taken into account. When sizing a complete cooling system, additional relevant heat loads and operating conditions must also be taken into account.
What additional heat loads must be taken into account?
In addition to the IT equipment, other components can introduce heat into the server room or the data center. Which of these are relevant depends on the specific building and facility design.
- UPS and power supply systems, provided their losses occur in the area under consideration,
- lighting and other electrical equipment,
- people,
- heat ingress through the building envelope or adjacent areas,
- heat losses from other technical components.
It is crucial to define a clear boundary for the calculation. Heat that is generated outside the area to be cooled and dissipated there, for example, should not automatically be included in the room cooling load.
Rated power or actual power consumption—which is decisive?
The sum of the rated or connected loads of all IT components does not necessarily have to match their actual power consumption during operation. Simply adding up all maximum manufacturer specifications can therefore lead to an unrealistic estimate.
If reliable operational data is available, it can serve as a valuable basis for the design. For new data centers, however, the planned IT equipment, expected utilization, and possible future performance increases must be taken into account.
At the same time, the cooling system must not be sized so tightly that foreseeable load conditions or expansions can no longer be safely managed.
Why is the power of individual racks important?
Two data centers can have the same total IT power and yet have very different cooling requirements. It is also crucial how the heat is distributed across the individual racks and the room. If high power levels are concentrated in just a few racks, local heat loads are created,
If high power outputs are concentrated in just a few racks, this creates local heat loads that must be dissipated using correspondingly large air volumes or other cooling methods. A more evenly distributed IT load, on the other hand, may place different demands on airflow and the cooling system.
Therefore, when planning, both the total IT power and the expected power per rack should be taken into account. Especially in the case of high-density applications, this consideration can be decisive for the choice between air cooling, liquid cooling, or a hybrid concept.
How are cooling capacity and airflow related?
In air-based cooling, heat is absorbed as the air flowing through the IT equipment warms up. The transferable heat load therefore depends, among other factors, on the airflow and the temperature difference between cold and heated air.
As IT performance increases, a correspondingly greater amount of heat must be dissipated. This can be achieved through higher airflow rates, a larger usable temperature difference, or a combination of both.
However, very high airflow rates require sufficiently large flow paths and corresponding fan capacity. For high rack power densities, it is therefore increasingly important to determine whether heat can still be effectively dissipated via air or whether a different or hybrid cooling concept is more suitable.
How are future expansions taken into account?
Data centers change over their service life. New servers may be more powerful, existing racks may be densely populated, and additional IT space may be added.
Such developments should be taken into account as early as the planning phase. However, this does not necessarily mean that all cooling components must be operated from day one to accommodate a distant, maximum expansion scenario.
Modular or scalable cooling concepts can allow the installed cooling capacity to grow along with the IT infrastructure. At the same time, sufficient space, connections, and technical capabilities should be provided for future expansions.
Why not simply size the cooling system as large as possible?
A large safety margin may seem advantageous at first, but it can lead to unnecessarily large systems and unfavorable operating conditions. In real-world operation, cooling units often operate for long periods of time in the partial-load range.
Therefore, design capacity, redundancy, and future reserve capacity should be distinguished from one another. The required redundancy serves to ensure operational reliability, while a capacity reserve accounts for future increases in demand.
The goal is a cooling system that reliably meets current and foreseeable demand while also being able to operate efficiently even under partial load.
What is crucial for the overall design?
The starting point for robust cooling planning is as realistic an assessment as possible of the IT heat load. Added to this are other relevant heat inputs, the spatial load distribution, and requirements for redundancy and future expansions.
Only then should it be determined what cooling capacity will be installed and how this heat is to be technically dissipated. Simply specifying a cooling capacity in kilowatts therefore does not yet describe a suitable cooling concept.
Particularly as rack power increases, cooling capacity, airflow, and power density must be considered together. This allows one to assess whether traditional air cooling is appropriate or whether other or hybrid cooling methods are required.
Server rooms and data centers do not need to be operated at the coldest possible temperature; rather, what matters most is that the IT equipment can operate reliably within the environmental conditions for which it is designed.
For cooling, this means that the temperature should be regulated so that the permissible conditions for the IT components are maintained, without wasting unnecessary energy on cooling the air too much.
What temperature is actually critical for IT?
For air-cooled servers, the most relevant temperature is the air temperature entering the IT components at the intake side. A single measure of room temperature therefore provides only a limited description of the actual conditions at the servers.
Different temperatures can occur within a data center; the air heats up as it flows through the IT equipment and is then recirculated for cooling. Warm return air is therefore not a problem at first, but rather a normal consequence of the absorbed heat.
The situation becomes critical when air that has already been heated re-enters the intake side of the servers, where the specified intake conditions are no longer met.
Why doesn’t a server room need to be as cold as possible?
Lower room temperatures do not automatically mean greater operational reliability. As long as the permissible operating conditions of the IT equipment in use are reliably maintained, unnecessarily intense cooling can simply result in additional energy consumption.
Higher permissible operating temperatures, on the other hand, can improve the efficiency of the cooling system. For example, the operating times for free cooling can increase, and the use of mechanical cooling can be reduced.
The goal should therefore not be the lowest possible temperature, but rather stable and energy-efficient operation within the permissible conditions.
What temperatures are recommended for data centers?
The ASHRAE Thermal Guidelines for Data Processing Environments provide important guidance on the climatic conditions in data centers. For air-cooled IT equipment in classes A1 through A4, a temperature range of 18 to 27 °C is recommended for regular operation. The key factor here is that these temperatures refer to the inlet air of the IT equipment. It is therefore not just any room temperature that matters, but the temperature of the air entering the IT equipment.
It is crucial to note that these temperatures refer to the inlet air of the IT equipment. The decisive factor is therefore not any arbitrary room temperature, but rather the temperature of the air drawn in by servers and other IT components.
In addition to the recommended range, ASHRAE defines significantly wider permissible temperature ranges depending on the equipment class. For Class A1, for example, 15 to 32 °C is specified as the permissible range, and for Class A2, 10 to 35 °C. For specially designed Class A3 and A4 devices, the permissible ranges are even wider. However, the permissible range should not be confused with the recommended
However, the permissible range should not be confused with the recommended operating range. The fact that an IT device is approved for higher inlet temperatures does not automatically mean that these temperatures are the best choice for the continuous operation of the entire data center. In concrete planning, therefore, in addition to the recommendations of ASHRAE, the permissible operating conditions of the actual IT hardware used must always be taken into account.
Therefore, when planning specific installations, in addition to the recommendations from ASHRAE, the permissible operating conditions of the actual IT hardware being used must always be taken into account.
Why is airflow just as important as temperature?
A low setpoint temperature cannot compensate for poor air flow. If cold and warm air mix uncontrollably, individual servers may receive inlet air that is too warm, even though the average room temperature appears normal.
Consistent separation of airflows is therefore an essential component of efficient IT cooling. Cold and hot aisles, as well as their enclosures, can help prevent short-circuiting between cold supply air and warm return air.
The better the airflow management works, the more precisely the cooling capacity can be directed to where it is actually needed.
Where should the temperature be measured?
A single temperature sensor on a wall or in the return air area is not sufficient to reliably assess the conditions at all IT components.
Measurements taken at the intake side of the racks are particularly relevant. When rack power ratings vary, multiple measurement points may be useful to identify local temperature differences and potential hotspots.
Temperature measurement is therefore not only important for monitoring. It also provides information for controlling the cooling system and can help avoid unnecessarily low cooling temperatures.
What role does humidity play?
In addition to temperature, humidity is also one of the environmental conditions affecting IT equipment.
The ASHRAE Thermal Guidelines also provide recommended operating ranges for humidity. In addition to relative humidity, the dew point is given particular consideration. For the specific design, temperature and humidity should therefore be evaluated together and compared with the requirements of the IT hardware in use. Temperature and humidity should therefore be considered together and
Temperature and humidity should therefore be considered together and monitored using appropriate sensors.
How does the choice of temperature affect energy efficiency?
The selected temperature conditions have a direct impact on the capabilities of the cooling system. The lower the required supply air temperature, the greater the effort required to provide cooling may become.
Conversely, if the temperature ranges permitted for IT are used sensibly, this can result in more favorable operating conditions for heat exchangers and refrigeration systems. Free cooling, in particular, can benefit from this, as it can be used for longer periods under suitable outdoor conditions. An energy-efficient temperature strategy therefore does not seek to find the lowest possible temperature, but rather a suitable operating range that combines IT security and energy efficiency.
An energy-efficient temperature strategy therefore does not seek to achieve the lowest possible temperature, but rather a suitable operating range that combines IT security and energy efficiency.
What is the key factor in determining the overall temperature?
The starting point is the permissible environmental conditions for the IT equipment used. Next, airflow, power density, sensors, the cooling system, and control mechanisms must be coordinated so that these conditions are reliably maintained.
In practice, this means, for example: If 24 °C is measured on the intake side of a server rack, this value falls within the temperature range recommended by ASHRAE for the specified air-cooled IT classes. Therefore, this temperature alone does not provide a reason to reduce the supply air temperature to, for example, 18 °C.
From an energy perspective, it may in fact make more sense to take full advantage of the permissible temperature conditions for the IT equipment. Higher cooling water temperatures and longer operating times for free cooling can reduce the energy requirements of data center cooling.
A small server room has different cooling requirements than a large data center. Applications with very high power densities—such as those found, for example, in high-performance computing (HPC) and modern AI hardware—are a distinct case.
The decisive factors here are not just the size of the room or the number of servers. Above all, IT performance, power density, desired availability, and future expansions determine which cooling concept is suitable.
What characterizes the cooling of a traditional server room?
Server rooms can be found, for example, in office buildings, government agencies, manufacturing facilities, or other companies that operate their IT infrastructure partially or entirely on-site.
Often, there are only a few racks in these spaces. The total heat load is therefore usually significantly lower than in a large data center. Nevertheless, the heat generated must be reliably dissipated.
A particular challenge can arise from the fact that server rooms were not originally designed for high heat loads. Limited ceiling heights, limited space for technical equipment, or a lack of installation space can restrict the choice of cooling system.
Compact cooling solutions tailored to the spatial conditions can be advantageous here.
What additional requirements arise in a data center?
In larger data centers, numerous racks and IT systems are operated together. Consequently, the total heat load and the demands on the technical infrastructure increase.
In addition to pure cooling capacity, the following factors play a particularly important role here: operational reliability, redundancy, energy efficiency, and controlled airflow. Maintenance work should also be possible without compromising the necessary cooling of the IT equipment.
At the same time, data centers evolve over the course of their service life. Cooling systems should therefore be designed, as far as possible, to ensure that expansions and changes to the IT infrastructure can be accommodated.
What does power density mean in a data center?
Power density describes how strongly the electrical—and thus thermal—power is concentrated on a specific area or on individual racks.
A data center with many racks carrying comparatively low loads can have a high total power output without generating exceptionally high heat loads on any single rack. If, on the other hand, very high-performance systems are concentrated in just a few racks, a correspondingly large amount of heat must be dissipated in a confined space. For cooling planning, therefore, it is not only the total power in kilowatts or megawatts that is relevant. Equally important is the question of how this power is distributed among the individual racks.
For cooling planning, therefore, it is not only the total power in kilowatts or megawatts that is relevant. Equally important is the question of how this power is distributed across the individual racks.
What Is High-Density IT?
The term “high-density IT” is used when high computing power and, consequently, high heat loads are concentrated in a comparatively small space. Typical applications can be found, for example, in high-performance computing and, increasingly, in systems for artificial intelligence.
There is no universally applicable threshold for rack power above which one must refer to it as high-density. Rather, the decisive factor is whether the resulting heat load can still be dissipated reliably and cost-effectively using the intended cooling concept.
As power per rack increases, air cooling requires larger volume of air. This places greater demands on fans, heat exchangers, airflow paths, and the separation of cold and warm air.
What are typical rack power levels?
The power of individual racks can vary greatly depending on the application. Traditional data centers were often designed for rack power in the single-digit or low double-digit kilowatt range.
In contrast, modern high-density IT can reach power levels of 50 kW per rack and significantly higher. With current AI and HPC systems, rack power levels of more than 100 kW are also possible.
Such figures illustrate why a cooling concept cannot be selected based solely on the total data center power. A data center with 1 MW of IT power and evenly distributed heat loads presents different challenges than a facility in which a large portion of this power is concentrated in just a few heavily loaded racks.
When does air cooling reach its limits?
Air can reliably transport large amounts of heat, but it requires a sufficient air volume to do so. As rack power increases, larger air volumes and adequately sized airflow paths therefore become necessary.
In traditional server rooms and many data center applications, air cooling remains a proven cooling method. Through good airflow management, sufficiently large heat exchanger surfaces, and a demand-based control system, even larger heat loads can be efficiently dissipated.
However, at very high power densities, the required airflow rate may become technically or economically impractical. In this range, liquid cooling and hybrid systems are becoming increasingly important.
Which cooling concept is the right one?
The size of a data center alone does not determine the appropriate cooling method. Key factors include the actual heat loads, their spatial distribution, the IT hardware used, and the requirements for availability and scalability.
For many server rooms and traditional data centers, air cooling remains a technically viable solution. For very high power densities, however, liquid cooling or hybrid systems may be necessary or advantageous.
Customized cooling solutions for different power densities
Since heat loads, space constraints, and requirements for operational reliability vary from data center to data center, even air-based cooling systems do not have to be designed according to a fixed standard scheme.
HANSA develops and manufactures cooling units specifically tailored to the respective project. Airflow capacity, heat exchanger surfaces, unit dimensions, airflow patterns, redundancy, and control systems can all be customized to meet the requirements of the data center.
This makes it possible to implement both compact solutions for server rooms and larger systems for data centers. Even large-scale cooling solutions based on the principle of a cooling wall can be implemented on a project-specific basis. can be implemented.